What the R-value means
An R-value is thermal resistance: how strongly a layer resists heat being conducted through it, measured in m²·K/W. Higher means more resistance and less heat flow. An R4.0 ceiling batt resists heat twice as well as an R2.0 batt of the same area. Resistances of layers stacked one behind the other add, so plasterboard, an air space and a batt each contribute to the total R-value of a ceiling or wall. The figure printed on a batt pack is the material R-value of the batt alone; the total R-value of the finished construction includes the other layers and is what energy ratings use.
U = 1 ÷ R Heat flow Q = U × A × ΔT
U is the conductance in W/m²·K: watts flowing through each square metre for every degree of temperature difference. A is the area in m² and ΔT the difference between inside and outside in °C. Because U is the inverse of R, the first R-value added does most of the work: going from R0.5 to R2.5 cuts the conduction through a wall from 2 to 0.4 W/m²·K, while adding a further R2.0 would only take it from 0.4 to 0.22.
How the batts are worked out
Wall area = wall length × height − openings
Area to insulate = element area × (1 − framing factor ÷ 100)
Packs = ⌈area to insulate × (1 + waste ÷ 100) ÷ pack coverage⌉
The framing factor is the share of the surface taken by timber, where no batt goes. A 45 mm-thick stud at 450 mm centres covers 45 ÷ 450 = 10% of a wall, and at 600 mm centres 45 ÷ 600 = 7.5%, before plates, noggings and doubled studs around openings, which push the real figure up. Pack coverage is printed on the pack in m²; packs are rounded up for each element because ceiling batts are thicker and are not the same product as wall batts. Cost is packs × price per pack, and a contingency percentage is added to the subtotal.
Worked example
The defaults describe a single-storey house: 100 m² of ceiling, 40 m of external wall 2.4 m high with 12 m² of windows and doors, and 60 m² of suspended floor. The framing factor is 10% and waste 5%. Every price and pack coverage here is an example, not a market rate.
- Ceiling. 100 × 0.9 = 90 m² to insulate; 90 × 1.05 = 94.5 m²; 94.5 ÷ 7 = 13.5, so 14 packs at $90 = $1,260.
- Walls. 40 × 2.4 = 96 m², less 12 m² of openings = 84 m²; 84 × 0.9 = 75.6 m²; 75.6 × 1.05 = 79.38 m²; 79.38 ÷ 9 = 8.82, so 9 packs at $70 = $630.
- Underfloor. 60 × 0.9 = 54 m²; 54 × 1.05 = 56.7 m²; 56.7 ÷ 9 = 6.3, so 7 packs at $65 = $455.
- Cost. $1,260 + $630 + $455 = $2,345, plus 10% contingency of $234.50, is $2,579.50.
- Heat flow, ceiling. Assuming R0.5 now, U = 1 ÷ 0.5 = 2 W/m²·K, or 2 × 100 = 200 W per °C over the ceiling. With R4.0 batts the total is 0.5 + 4 = 4.5, U = 1 ÷ 4.5 = 0.222 W/m²·K and 22.2 W per °C: 88.9% less.
- Walls and floor. The walls go from 2 × 84 = 168 W per °C to 84 ÷ 3 = 28 W per °C (83.3% less) and the floor from 120 to 60 ÷ 2.5 = 24 W per °C (80% less). For the whole house, 488 W per °C falls to 74.2 W per °C, so on a day 10 °C colder outside than in, conduction through these surfaces drops from about 4,880 W to about 742 W in this simplified picture.
Minimum R-values and climate zones
The minimum total R-values a new home or extension must reach are set by the National Construction Code (NCC) and depend on the NCC climate zone, whether the heat flow to resist is mostly upward or downward, and the construction. They are not quoted here: look them up for your address in the NCC Housing Provisions published by the Australian Building Codes Board at ncc.abcb.gov.au, and read the Australian Government's guide at yourhome.gov.au on choosing and installing insulation. Your state may also have its own scheme, such as BASIX in New South Wales.
Where the simple numbers stop being reliable
Framing is a thermal bridge. Timber has a much lower R-value than a batt of the same thickness, and steel framing is far worse, so a wall's real total R-value is lower than the batt's figure suggests. The heat-flow table ignores this; a proper total R-value calculation weights the framed and insulated paths by area.
Compression and gaps. A batt squashed into a cavity shallower than its thickness loses resistance, and gaps around the edges let heat bypass it. Check that the batt thickness fits the stud or joist depth.
Safety. Keep insulation clear of downlights, transformers, flues and other heat sources, follow the manufacturer's clearances, and switch off power before working in the roof space. Conductive foil laid near electrical wiring is an electrocution risk, so have foil products installed by a qualified installer.