BTU Calculator

Get a rough heating or cooling capacity for one room, in kilowatts, BTU per hour and tons of refrigeration. It is a rule of thumb based on floor area, adjusted for ceiling height, insulation, sun, people and climate, and every assumption it uses is shown and can be changed. For buying a system, a professional heat-load calculation is more reliable.

Last updated .

The room

Sizing for
Units
m
m
m

For cooling, severe means hot summers.

Rule-of-thumb assumptions (editable)

These figures are assumptions, not standards. Change any of them to match a guide you trust. See why rules of thumb disagree.

W/m²
W/m²
m
BTU/h
BTU/h

Average insulation, a moderate climate and average sun use a factor of 1. The shade, sun, people and kitchen figures follow the ENERGY STAR guidance for sizing room air conditioners and are used for cooling only.

Result

Rough cooling capacity

–

–Kilowatts
–BTU per hour
–Tons of refrigeration
–Watts per m² of floor
PartWattsBTU/h

Rule of thumb only. A professional heat-load calculation, which accounts for the walls, windows, orientation, air leakage and local design temperatures, is more reliable. Treat this figure as a starting point for that conversation.

Show the working

    The rule-of-thumb method

    A heater or air conditioner has to replace the heat a room loses, or remove the heat it gains. Working that out properly means adding up the heat flow through every wall, window, floor and ceiling, plus air leakage and the heat from people and appliances. A rule of thumb skips all of that and assumes the load is roughly proportional to floor area, then nudges the answer for the things that matter most. That is what this calculator does.

    Q = A × b × (h ÷ h₀) × fins × fclim × fsun + people allowance + kitchen allowance

    A is the floor area, length times width. b is the allowance per unit of floor area. h is the ceiling height and h₀ the height the allowance assumes, so a taller room with more air and wall gets proportionally more. The f values are multipliers for insulation, climate and sun, each 1 for an average room. For heating, the sun, people and kitchen terms are left out: they add heat, so ignoring them errs on the side of a larger heater.

    The default cooling allowance is 63 W/m², which is about 20 BTU per hour per square foot, a figure often quoted in US guides. The default heating allowance of 95 W/m² (about 30 BTU per hour per square foot) is an example for a moderate climate. The shade and sun adjustments of 10% down and 10% up, 600 BTU per hour for each person beyond two, and 4,000 BTU per hour for a kitchen follow the ENERGY STAR guidance for sizing room air conditioners. The insulation and climate factors are this calculator's own assumptions, chosen to show the effect, and you can change them.

    kW = W ÷ 1,000   BTU/h = kW × 3,412.14   tons = BTU/h ÷ 12,000

    A BTU per hour is a rate of heat flow, and 1 kW is 3,412.14 BTU/h using the International Table BTU. One ton of refrigeration is defined as 12,000 BTU/h, the rate at which a short ton of ice absorbs heat when it melts over 24 hours. Many air conditioners are labelled in BTU/h or tons in the US and in kW in Australia; the conversion is exact either way.

    Worked examples

    Default room, cooling. A 5 m by 4 m room with a 2.4 m ceiling, average insulation and sun, two people and a moderate climate.

    1. Area: 5 × 4 = 20 m².
    2. Base load: 20 × 63 = 1,260 W. The height factor is 2.4 ÷ 2.4 = 1 and every other factor is 1.
    3. Convert: 1.26 kW × 3,412.14 = 4,299 BTU/h, which is 4,299 ÷ 12,000 = 0.36 tons.

    A harder room. The same floor with a 2.7 m ceiling, poor insulation, lots of sun and four people. The height factor is 2.7 ÷ 2.4 = 1.125, so the base becomes 20 × 63 × 1.125 × 1.3 × 1.1 = 2,027 W. Two extra people add 1,200 BTU/h, which is 351.7 W. The total is 2,378.7 W, about 2.38 kW or 8,116 BTU/h, nearly twice the first room.

    Heating. The default room in a severe climate needs 20 × 95 × 1.2 = 2,280 W, or 2.28 kW (7,780 BTU/h).

    Imperial. A 12 ft by 15 ft room with an 8 ft ceiling, using 20 BTU/h per square foot and an 8 ft reference height, needs 180 × 20 = 3,600 BTU/h, which is 1.06 kW or 0.3 tons.

    Why rules of thumb disagree

    Search for a sizing rule and you will find figures that differ by a factor of two or more. They are not all wrong; they answer different questions.

    A proper load calculation, such as the ACCA Manual J method used in the United States or a heat-load assessment by an installer, replaces those hidden assumptions with your room's actual construction and local design temperatures. Use this calculator to understand the scale of the answer and to sense-check a quote, not to replace that.