The rule-of-thumb method
A heater or air conditioner has to replace the heat a room loses, or remove the heat it gains. Working that out properly means adding up the heat flow through every wall, window, floor and ceiling, plus air leakage and the heat from people and appliances. A rule of thumb skips all of that and assumes the load is roughly proportional to floor area, then nudges the answer for the things that matter most. That is what this calculator does.
Q = A × b × (h ÷ h₀) × fins × fclim × fsun + people allowance + kitchen allowance
A is the floor area, length times width. b is the allowance per unit of floor area. h is the ceiling height and h₀ the height the allowance assumes, so a taller room with more air and wall gets proportionally more. The f values are multipliers for insulation, climate and sun, each 1 for an average room. For heating, the sun, people and kitchen terms are left out: they add heat, so ignoring them errs on the side of a larger heater.
The default cooling allowance is 63 W/m², which is about 20 BTU per hour per square foot, a figure often quoted in US guides. The default heating allowance of 95 W/m² (about 30 BTU per hour per square foot) is an example for a moderate climate. The shade and sun adjustments of 10% down and 10% up, 600 BTU per hour for each person beyond two, and 4,000 BTU per hour for a kitchen follow the ENERGY STAR guidance for sizing room air conditioners. The insulation and climate factors are this calculator's own assumptions, chosen to show the effect, and you can change them.
kW = W ÷ 1,000 BTU/h = kW × 3,412.14 tons = BTU/h ÷ 12,000
A BTU per hour is a rate of heat flow, and 1 kW is 3,412.14 BTU/h using the International Table BTU. One ton of refrigeration is defined as 12,000 BTU/h, the rate at which a short ton of ice absorbs heat when it melts over 24 hours. Many air conditioners are labelled in BTU/h or tons in the US and in kW in Australia; the conversion is exact either way.
Worked examples
Default room, cooling. A 5 m by 4 m room with a 2.4 m ceiling, average insulation and sun, two people and a moderate climate.
- Area: 5 × 4 = 20 m².
- Base load: 20 × 63 = 1,260 W. The height factor is 2.4 ÷ 2.4 = 1 and every other factor is 1.
- Convert: 1.26 kW × 3,412.14 = 4,299 BTU/h, which is 4,299 ÷ 12,000 = 0.36 tons.
A harder room. The same floor with a 2.7 m ceiling, poor insulation, lots of sun and four people. The height factor is 2.7 ÷ 2.4 = 1.125, so the base becomes 20 × 63 × 1.125 × 1.3 × 1.1 = 2,027 W. Two extra people add 1,200 BTU/h, which is 351.7 W. The total is 2,378.7 W, about 2.38 kW or 8,116 BTU/h, nearly twice the first room.
Heating. The default room in a severe climate needs 20 × 95 × 1.2 = 2,280 W, or 2.28 kW (7,780 BTU/h).
Imperial. A 12 ft by 15 ft room with an 8 ft ceiling, using 20 BTU/h per square foot and an 8 ft reference height, needs 180 × 20 = 3,600 BTU/h, which is 1.06 kW or 0.3 tons.
Why rules of thumb disagree
Search for a sizing rule and you will find figures that differ by a factor of two or more. They are not all wrong; they answer different questions.
- Different buildings and climates. A rule written for well-insulated houses in a mild region will undersize a room in an old house in a hot one. The allowance per square metre hides the building's walls, windows and air tightness.
- Different safety margins. Some rules are deliberately generous so that a unit is never too small. An oversized air conditioner, though, cycles on and off and can remove less humidity, so bigger is not automatically better.
- Area or volume. Some rules scale by floor area, some by room volume. They agree only at the ceiling height the rule assumes.
- Rated and real capacity. A heat pump's output changes with the outdoor temperature, so a unit's nameplate figure is measured at standard test conditions, which may not match your coldest or hottest days.
- Units. BTU (an amount of energy) and BTU/h (a rate) are often mixed up, as are kW of heating or cooling output and kW of electricity input. A unit with 2.5 kW of cooling output may draw well under 1 kW of electricity.
A proper load calculation, such as the ACCA Manual J method used in the United States or a heat-load assessment by an installer, replaces those hidden assumptions with your room's actual construction and local design temperatures. Use this calculator to understand the scale of the answer and to sense-check a quote, not to replace that.