CalcTrace

Voltage Drop Calculator

Work out how much voltage is lost along a cable run from the current, the one-way length, the conductor material and its cross-section in mm² or AWG. Covers DC and single-phase circuits and balanced three-phase circuits, and gives the drop in volts and as a percentage of the supply.

Last updated .

Circuit and cable

Circuit
V
A

For three-phase, enter the line-to-line voltage and the current in each line.

The distance from the supply to the load, not the total length of wire. The calculator allows for the return path.

Area of one conductor. For AWG, type a gauge from 40 to 0, or 1/0 to 4/0 (also written 0, 00, 000, 0000).

°C
%

Resistance rises as the cable warms under load. The allowed drop is whatever limit applies to your installation under your local wiring rules; the calculator does not assume one.

Result

Voltage drop

–

–Drop as % of supply
–Voltage at the load
–Resistance per conductor
–Power lost in the cable

Safety. This is an estimate for planning. Mains wiring must follow your local electrical standards and be done by a licensed electrician, who will also check current-carrying capacity, protection and installation method, which this calculator does not.

Show the working

    How voltage drop is calculated

    Every conductor has resistance, so current flowing through it loses some voltage on the way to the load. The resistance of a conductor is set by its material, its length and its cross-sectional area.

    R = ρ × L ÷ A × (1 + α × (T − 20))

    R is the resistance of one conductor in ohms, ρ (rho) is the resistivity of the material at 20 °C in Ω·mm²/m, L is the one-way length in metres, A is the cross-section of one conductor in mm², α (alpha) is the temperature coefficient of resistance per °C and T is the conductor temperature in °C. The drop then depends on the circuit:

    Single-phase or DC:  Vd = 2 × I × R

    Three-phase (balanced):  Vd = √3 × I × R

    Percentage drop = Vd ÷ Vsupply × 100

    I is the load current in amperes. In a single-phase or DC circuit the current flows out along one conductor and back along the other, so the drop is across twice the one-way length. In a balanced three-phase circuit no current returns in the neutral; the drop between lines is √3 (about 1.732) times the drop in one conductor, and it is compared with the line-to-line supply voltage.

    Resistivity values used

    Copper: 0.017241 Ω·mm²/m at 20 °C, which is 1/58. This is the International Annealed Copper Standard value, set out in IEC 60028, with a temperature coefficient of 0.00393 per °C. Aluminium: 0.028264 Ω·mm²/m at 20 °C, the value for hard-drawn aluminium wire in IEC 60889, with a coefficient of 0.00403 per °C. Real cable conductors can differ slightly, so choose “Other” to enter the figure from a manufacturer’s data sheet.

    Worked example: 20 A over 30 m of 2.5 mm² copper

    1. Resistance of one conductor. R = 0.017241 × 30 ÷ 2.5 = 0.20690 Ω at 20 °C.
    2. Single-phase drop. Vd = 2 × 20 × 0.20690 = 8.276 V.
    3. As a percentage. On a 230 V supply that is 8.276 ÷ 230 × 100 = 3.598%, leaving 221.72 V at the load.
    4. Power lost in the cable. I² × 2R = 400 × 0.41379 = 165.5 W, given off as heat along the run.
    5. The same cable on three-phase. With 20 A in each line of a 400 V system, Vd = 1.732 × 20 × 0.20690 = 7.167 V, which is 1.792% of 400 V.

    Choosing a size for a limit. Rearranging gives the smallest area that keeps the drop within a limit: A = k × I × ρ × L ÷ Vd,max, where k is 2 for single-phase and √3 for three-phase. Suppose the limit that applies to your installation were 3% of 230 V, or 6.9 V. Then A = 2 × 20 × 0.017241 × 30 ÷ 6.9 = 2.999 mm², so 2.5 mm² is too small and the next common size, 4 mm², gives 5.172 V or 2.249%. Enter your own limit above and the calculator does this step for you.

    Converting AWG to mm²

    American Wire Gauge sizes follow a geometric rule defined in ASTM B258. Gauge 36 is 0.005 inch (0.127 mm) across, gauge 0000 is 0.46 inch (11.684 mm), and there are 39 steps between them, each multiplying the diameter by the same ratio.

    d = 0.127 × 92(36 − n) ÷ 39 mm  and  A = π ÷ 4 × d²

    n is the gauge number, with 0 for 1/0, −1 for 2/0, −2 for 3/0 and −3 for 4/0. For 10 AWG, d = 0.127 × 9226/39 = 2.588 mm and A = 5.261 mm². Other common sizes: 14 AWG is 2.081 mm², 12 AWG is 3.309 mm², 8 AWG is 8.366 mm², 6 AWG is 13.30 mm² and 4/0 is 107.2 mm². A drop of three gauge numbers roughly doubles the area. The formula gives solid-wire sizes; stranded conductors of the same gauge have a similar copper area.

    Common mistakes and limits of the method

    Doubling the length twice. Enter the one-way distance. The factor of 2 for the return conductor is already in the formula, so entering the loop length doubles the answer.

    Ignoring temperature. Resistivity values are quoted at 20 °C. A copper conductor running at 70 °C has 1 + 0.00393 × 50 = 1.1965 times the resistance, so the example above becomes 9.902 V, or 4.305%. Use the temperature box for a cable that runs warm.

    Using the wrong voltage on three-phase. The √3 formula gives the line-to-line drop, so compare it with the line-to-line voltage. For a single-phase load connected line to neutral on a three-phase system, use the single-phase setting and the line-to-neutral voltage.

    Large cables and AC. The method uses resistance only. In large AC cables, reactance and the load’s power factor add to the drop, and full calculations use impedance tables from the cable standard. Treat the result as a lower bound for big conductors.

    Motor starting. Motors draw several times their running current for a moment when they start. Check the drop at that current too if the voltage at start-up matters.

    Voltage drop is not the only test. A cable must also carry the current without overheating, and its protection must operate correctly under fault conditions. Those depend on the installation method and the rules where you live. Wiring must follow local electrical standards and be done by a licensed electrician.